1-ch RTD Input Module

Model No:
ADAM-4013
Highlights:
  • Accuracy +/- 0.1% or better
  • Built-in Watchdog Timer
  • Isolation Voltage 3000 VDC
  • Sampling Rate 10 sample/sec
QTY:
Downloads:
Overview

Analog input modules use a microprocessor-controlled integrating A/D converter to convert sensor voltage, current, or RTD signals into digital data. The digital data is then translated into either engineering units, twos complement hexadecimal format or percentage of full-scale range (FSR) according to the module’s configuration.

When prompted by the host computer, the data is sent through a standard RS-485 interface. The Analog Input Modules offer signal conditioning, A/D conversion, ranging, and RS-485 digital communication functions. They protect your equipment from ground loops and power surges by providing opto-isolation of the A/D input and transformer based isolation up to 3000 V DC.

Main Features
  • Power Supply: 10~30 VDC
Analog Input
  • Channels: 1 (2, 3, or 4-wired)
  • Direct Sensor Input: RTD (Pt, or Ni)
  • Sampling Rates: 10 samples/second
  • Resolution: 16-bit
  • Input Impedance: 2 MOhm
  • Span Drift: ±25 ppm/°C
  • Zero Drift: ±3 µV/°C
  • CMR @ 50/60 Hz: 150 dB
  • NMR @ 50/60 Hz: 100 dB
 
General
  • Watchdog Timer: System (1.6 second)
  • Connector: 1 x plug-in terminal block (#14~22 AWG)
  • Temperature (Operating)  -10~70 °C (14~158 °F)
  • Humidity: 5~95 %RH
  • Temperature (Storage) -25~85 °C (-13~185 °F)
  • Interface: RS-485
  • Isolation Protection: 3000 VDC
  • Communication Protocol: ASCII command
  • Communication Speed: Serial: From 1,200 to 115.2 k
  • Comm. Distance: Serial: 1.2 km
  • Data Flow Control: Yes
 
Ordering Info
  • ADAM-4013 - 1-ch RTD Input Module

Want A Quote? Get In Touch

Call our experts today for friendly advice on
+1 864 421 6991