Advantech ADAM-4118 Robust 8-ch Thermocouple Input Module with Modbus

Advantech ADAM-4118 Robust 8-ch Thermocouple Input Module with Modbus

ADAM-4118

  • 8 differential & independent thermocouple configuration channels
  • Wide operating temperature range
  • 1 kV surge protection on power inputs, 3 kV EFT, and 8 kV ESD protection
  • Wide power input range: +10~+48 VDC
  • Supports filter auto-tuning or filter out 50 Hz / 60 Hz
  • Online firmware update
-
+

Details

Advantech’s ADAM-4118 is a thermocouple input module with 8 differential & independent thermocouple configuration channels. The module has a wide power input and operating temperature and online firmware updating.

Downloads

System Integration

Please ask about how we can configure your solution

Global Operations

We ship and support products via offices globally

Full Warranty

Industry leading warranties on all solutions as standard

Technical Support

Experienced engineers are on hand to support your project

Can't Find What You Want?

Specification

  • Power Requirement: 10~48 VDC
  • Analog Input
  • Channels: 8 differential
  • Voltage Range: 15 mV ±50 mV ±100 mV ±500 mV ±1 V ±2.5 V
  • Current Input: ±20 mA 4~20 mA
  • Direct Sensor Input: J, K, T, E, R, S, B Thermocouple
  • Burn-out Detection: Yes (4~20 mA & all T/C)
  • Channel Independent Configuration: Yes
  • Sampling Rates: 10/100 samples/second (total)
  • Resolution: 16-bit
  • Input Impedance: Voltage: 20 MOhm Current: 120 Ohm
  • Span Drift: ±25 ppm/°C
  • Zero Drift: ±6 µV/°C
  • CMR @ 50/60 Hz: 92 dB
  • NMR @ 50/60 Hz: 60 dB
  • High Common Mode: 200 VDC
  • Watchdog Timer: System (1.6 second) & Communication
  • Connector: 2 x plug-in terminal block (#14~22 AWG)
  • Temperature (Operating): -40~85°C (40~185 °F)
  • Humidity: 5~95 %RH
  • Temperature (Storage): -40~85°C (40~185 °F)
  • Interface: RS-485
  • Isolation Protection: 3000 VDC
  • Communication Protocol: ASCII command & Modbus/RTU
  • Communication Speed: Serial: From 1,200 to 115.2 k
  • Data Flow Control: Yes