Advantech ADAM-4015 6-ch RTD Module with Modbus

Advantech ADAM-4015 6-ch RTD Module with Modbus

ADAM-4015

  • 6-channel 2 or 3 wires RTD Input
  • Accept Pt100/1000, Balco500, Ni input signals
  • Channels configurable for different types of input individually
  • Wiring burned-out detectable function
  • 3000 VDC A/D to logic isolation
-
+

Details

Advantech’s ADAM-4015 is an RTD module ideal for temperature measurement. Unlike traditional designs, the ADAM-4015 provides 6 x RTD input channels for different types of RTD signal making it a cost-effective solution in industrial & building automation.

The ADAM-4015 provides a broken wiring detection function so users can easily troubleshoot broken wiring problems.

Downloads

System Integration

Please ask about how we can configure your solution

Global Operations

We ship and support products via offices globally

Full Warranty

Industry leading warranties on all solutions as standard

Technical Support

Experienced engineers are on hand to support your project

Can't Find What You Want?

Specification

  • Power Supply: 10~30 VDC
  • Analog Input
  • Channels: 6 (2 or 3-wired)
  • Direct Sensor Input: RTD (Pt, Balco, or Ni)
  • Burn-out Detection: Yes
  • Sampling Rates: 10 samples/second
  • Resolution: 16-bit
  • Input Impedance: 10 MOhm
  • Span Drift: ±25 ppm/°C
  • Zero Drift: ±3 µV/°C
  • CMR @ 50/60 Hz: 120 dB
  • NMR @ 50/60 Hz: 100 dB
  • Watchdog Timer: System (1.6 second) & Communication
  • Connector: 2 x plug-in terminal block (#14~28 AWG)
  • Temperature (Operating): -10~70 °C (14~158 °F)
  • Humidity: 5~95 %RH
  • Temperature (Storage): -25~85 °C (-13~185 °F)
  • Interface: RS-485
  • Isolation Protection: 3000 VDC
  • Communication Protocol: ASCII command & Modbus/RTU
  • Communication Speed: Serial: From 1,200 to 115.2 k
  • Data Flow Control: Yes